Powerficient® specialized tap boxes are designed to securely channel currents while offering advanced safety interrupt systems. They safeguard electrical components and connections along your overhead power distributionsystem with precision. Our tap boxes are fully customizable, encompassing a range of configurations and component options.
Each unit includes essential features such as breakers or fuses, dropcords with a multiple connector options, locking wheels for added busway attachment stability, and metering capabilities. Moreover, they feature a modular enclosure that facilitates flexibility, enabling seamless adaptation to various configurations and requirements.
Rated Voltage: 347VAC L-N (fused) or 240VAC L-N (circuit breakers) for single-phase versions. 600VAC L-L available for fused 3-phase versions.
System: WYE (single-phase loads) 3-phase available on request.
Rated Current: 2x 60A (2X 48A continuous) @ 40 deg C
SCCR: 45kA
LS Cable & System’s Data-way for Data Centers is a system that can satisfy your requirements and continuously respond to the changing distribution environment. LS cable & system’s Data-way reduces time and cost loss incurred by cable extensions and IT rack relocation. Data-way is a solution to maximizing energy efficiency and stable power supply to your Data Center.
High Current Density: The Busway has a compact design compared to the existing models by using an effective heat-radiating housing profile and can carry from 160A up to 800A with reduced loss of electric power.
Eco-Friendly: Data-way acquired RoHS certification. Only using components without hazardous substances such as lead, cadmium, mercury and chrome.
Connection: Kit: DH (dual head) bolts & Visible-label (Redtag) Check for installation using the contact.
Permissible Operating Temperature: The cross sectional areas of the conductor and housing profile are designed to meet the standard permissible operating temperature of IEC 61439-1, 6 or UL 857. Therefore the temperature rise limit of the housing is within 55K or less of the ambient temperature.
Conductors: Data-Way uses either copper conductors with conductivity over 99%, or aluminum conductors with conductivity over 61%. U shape of conductor enables the Data-way to achieve the best performance and easy distribution.
Housing/Distribution: Data-Way uses an effective heat radiating aluminum housing which produces an excellent mechanical strength and heat radiation.
Conductor | Ampere | Height (MM) | Width (mm) | Weight |
|---|---|---|---|---|
AL | 160 | 52 | 150 | 7 |
AL | 250 | 52 | 150 | 7 |
AL | 400 | 87 | 150 | 11 |
AL | 630 | 87 | 150 | 14 |
CU | 160 | 52 | 150 | 10 |
CU | 250 | 52 | 150 | 10 |
CU | 400 | 67 | 150 | 15 |
CU | 630 | 87 | 150 | 21 |
CU | 800 | 87 | 150 | 27 |
Conductor | Rating (A) | Length(mm) | # of Plug IN Hole (Open Channel) | # of Plug IN Hole (Plug In Hole) | Weight (kg/m) |
|---|---|---|---|---|---|
AL | 160A | 3000 | - | 6v | 7 |
AL | 250A | 3000 | - | 6v | 7 |
AL | 400A | 3000 | - | 6v | 9 |
AL | 630A | 3000 | - | 6v | 12 |
CU | 160A | 3000 | - | 6v | 10 |
CU | 250A | 3000 | - | 6v | 10 |
CU | 400A | 3000 | - | 6v | 11 |
CU | 630A | 3000 | - | 6v | 15 |
CU | 800A | 3000 | - | 46v | 21 |
Conductor | Ampere | Mounting | Connection | Size (MM) W X H X D | Weight (kg/m) |
|---|---|---|---|---|---|
AL | 160 | Hanging | Terminals | 450 x 300 x 350 | 9 |
AL | 250 | Hanging | Terminals | 450 x 300 x 350 | 9 |
AL | 400 | Hanging | Terminals | 450 x 335 x 350 | 10 |
AL | 630 | Hanging | Terminals | 450 x 335 x 350 | 11 |
CU | 160 | Hanging | Terminals | 450 x 300 x 550 | 10 |
CU | 250 | Hanging | Terminals | 450 x 300 x 550 | 10 |
CU | 400 | Hanging | Terminals | 450 x 335 x 550 | 11 |
CU | 630 | Hanging | Terminals | 450 x 335 x 700 | 13 |
CU | 800 | Hanging | Terminals | 450 x 335 x 700 | 16 |
Conductor | Ampere | 10-3Ω / 100m, 60Hz - R | 10-3Ω / 100m, 60Hz - X | 10-3Ω / 100m, 60Hz - Z | Vd potential drop(V/100m) - 0.7 | Vd potential drop(V/100m) - 0.8 | Vd potential drop(V/100m) - 0.9 | Vd potential drop(V/100m) - 1.0 |
|---|---|---|---|---|---|---|---|---|
AL | 160 | 23.52 | 7.35 | 24.64 | 6.02 | 6.44 | 6.75 | 6.52 |
AL | 250 | 23.52 | 7.35 | 24.64 | 9.40 | 10.06 | 10.55 | 10.19 |
AL | 400 | 9.98 | 4.75 | 11.05 | 7.19 | 7.66 | 7.66 | 6.91 |
AL | 630 | 6.78 | 5.67 | 8.24 | 8.82 | 8.88 | 8.88 | 7.40 |
CU | 160 | 17.20 | 7.42 | 18.74 | 4.81 | 5.19 | 5.19 | 4.77 |
CU | 250 | 17.20 | 7.42 | 18.74 | 7.51 | 8.11 | 8.11 | 7.45 |
CU | 400 | 9.12 | 5.92 | 10.87 | 7.35 | 7.47 | 7.47 | 6.32 |
CU | 630 | 6.21 | 4.75 | 7.82 | 8.45 | 8.36 | 8.36 | 6.78 |
CU | 800 | 4.29 | 4.67 | 6.34 | 8.78 | 8.17 | 8.17 | 5.95 |
Ampere | AL(kA) 3 Cycles | Cu (ka) 3 Cycles |
|---|---|---|
160 | 22 | 22 |
250 | 22 | 22 |
400 | 30 | 22 |
630 | 30 | 53 |
800 | - | 35 |
Ampere | Bus Bar MAterial | SCCR (KA) | SCCr With Mccb (ka)* |
|---|---|---|---|
160 | Copper | 22 | 50 |
250 | Copper | 22 | 50 |
400 | Copper | 22 | 50 |
630 | Copper | 35 | - |
800 | Copper | 35 | - |
160 | Aluminum | 22 | 50 |
250 | Aluminum | 22 | 50 |
400 | Aluminum | 30 | 50 |
630 | Aluminum | 30 | - |
*LS Electric UTS600 600AF